Choosing HEPA and ULPA filtration
Specify the filter class together with airflow, pressure loss, housing and testing requirements.
Quick answer
Flow Dynamics supplies healthcare and clean-room filtration equipment in the UAE. EN 1822 classifies filters at the most penetrating particle size (MPPS), with minimum overall efficiencies of 99.95% for H13, 99.995% for H14 and 99.9995% for U15. These are filter-test values, so airflow, pressure loss, housing and installed-system testing must also be specified for the project.
Read the classification correctly
EN 1822 classifies high-efficiency filters at the most penetrating particle size (MPPS). Minimum overall efficiencies are 99.95% for H13, 99.995% for H14 and 99.9995% for U15. These values describe a filter test, not the cleanliness of an entire room.
Match the room specification
Use the project’s contamination-control requirements to select the class. Compare rated airflow, pressure drop and filter dimensions together. Filtration class alone does not determine room pressure, air distribution or installed-system performance.
Specify the housing and maintenance method
Gaskets, seals and installation quality affect bypass leakage. Where the risk assessment requires controlled filter replacement, BIBO housings provide a bag-based change method. Access, isolation and the approved change procedure remain part of the design.
Separate factory and installation tests
Obtain the specified manufacturer test documentation. Plan any installed-system integrity tests, acceptance criteria and maintenance checks required by the project. A factory classification does not replace verification of the installed arrangement.
Common questions
Should every project use the highest filter class?
Select the class required by the application and compare the complete system duty. Higher efficiency does not by itself establish the right airflow, pressure drop or maintenance arrangement.
Does UV-C replace HEPA filtration?
UV-C inactivation does not remove particles. UV treatment and particulate filtration serve different functions and may be specified together.